Potřebujeme váš souhlas k využití jednotlivých dat, aby se vám mimo jiné mohly ukazovat informace týkající se vašich zájmů. Souhlas udělíte kliknutím na tlačítko „OK“.
Standard Test Method for Evaluating the Resistance to Thermal Transmission of Materials by the Guarded Heat Flow Meter Technique
Automaticky přeložený název:
Standardní zkušební metoda pro hodnocení odolnosti vůči prostupu tepla materiálů střeženého měřidla tepelného toku Technika
NORMA vydána dne 15.8.2011
Označení normy: ASTM E1530-11
Poznámka: NEPLATNÁ
Datum vydání normy: 15.8.2011
Kód zboží: NS-42087
Počet stran: 9
Přibližná hmotnost: 27 g (0.06 liber)
Země: Americká technická norma
Kategorie: Technické normy ASTM
Keywords:
heat flow meter, heat flux transducer, thermal conductance, thermal conductivity, thermal resistance, thin specimen: Thermal transmission properties--steady-state, Thin material specimens/applications, Composites, Heat flow meter method, Heat flux transducer (HFT), Thermal conductance/conductivity, Thermal resistance/resistivity
Significance and Use | ||||||||||||||
This test method is designed to measure and compare thermal properties of materials under controlled conditions and their ability to maintain required thermal conductance levels. |
||||||||||||||
1. Scope | ||||||||||||||
1.1 This test method covers a steady-state technique for the determination of the resistance to thermal transmission (thermal resistance) of materials of thicknesses less than 25 mm. For homogeneous opaque solid specimens of a representative thickness, thermal conductivity can be determined (see Note 1). This test method is useful for specimens having a thermal resistance in the range from 10 to 400 × 10-4 m2·K·W-1, which can be obtained from materials of thermal conductivity in the approximate range from 0.1 to 30 W·m-1·K-1 over the approximate temperature range from 150 to 600 K. It can be used outside these ranges with reduced accuracy for thicker specimens and for thermal conductivity values up to 60 W·m-1·K-1. Note 1—A body is considered homogeneous when the property to be measured is found to be independent of specimen dimensions. 1.2 This test method is similar in concept to Test Method C518, but is modified to accommodate smaller test specimens, having a higher thermal conductance. In addition, significant attention has been paid to ensure that the thermal resistance of contacting surfaces is minimized and reproducible. 1.3 The values stated in SI units are to be regarded as standard. The additional values are mathematical conversions to inch-pound units that are provided for information only and are not considered standard. 1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. |
||||||||||||||
2. Referenced Documents | ||||||||||||||
|
Chcete mít jistotu o platnosti užívaných předpisů?
Nabízíme Vám řešení, abyste mohli používat stále platné (aktuální) legislativní předpisy.
Chcete vědět více informací? Podívejte se na tuto stránku.
Poslední aktualizace: 20.07.2024 (Počet položek: 2 338 064)
© Copyright 2024 NORMSERVIS s.r.o.